Chapter 2 Installation Instruction
Load route rated
current
20A
25A
Note:
1. The specs are applicable at ambient temperature of 25°C.
2. The battery cable should reach at least +90°C heat durability. It is recommended to use double-insulated copper-core
flame-retardant cable as battery cable
The CSA of the system earth cable should be the same as that of the largest power distribution cable and not less
2
than 1.5mm
. The earth terminal is one M5 bolt.
2. Cable specifications of NetSure 211 C45-S2 power supply system
It is recommended to use the RVVZ cables as AC cables. The cable should reach at least +70°C temperature
durability. Select the AC cable Cross-Sectional Area (CSA) according to Table 2-4.
Connector
AC input MCB
The CSA of DC cable depends on the current flowing through the cable, the allowable voltage drop and load peak
current. The recommended load peak current is 1/2 to 2/3 of MCB or fuse capacity.
Select the battery cable CSA according to Table 2-5. Select the load cable CSA according to Table 2-6.
Battery MCB
rated current
63A
Note:
1. The specs are applicable at ambient temperature of 25°C.
2. The battery cable should reach at least +90°C heat durability. It is recommended to use double-insulated copper-core
flame-retardant cable as battery cable
Load route rated
current
20A
10A
Note:
1. The specs are applicable at ambient temperature of 25°C.
2. The battery cable should reach at least +90°C heat durability. It is recommended to use double-insulated copper-core
flame-retardant cable as battery cable
The CSA of the system earth cable should be the same as that of the largest power distribution cable and not less
2
than 1.5mm
. The earth terminal is one M5 bolt.
Table 2-3 Load cable CSA selection
Max. output
Min. cable
current
CSA
2
2.5mm
20A
AWG12
2
2.5mm
25A
AWG12
Table 2-4 AC cable CSA selection
Table 2-5 Battery cable CSA selection
Max. battery
Min. cable
current
CSA
2
10mm
60A
AWG6
Table 2-6 Load cable CSA selection
Max. output
Min. cable
current
CSA
2
2.5mm
20A
AWG12
2
1.5mm
10A
AWG14
NetSure 211 C45 Embedded Power Supply System User Manual
Max. cable length (volt
drop: 0.5V, with min. CSA)
3.1m
4.6m
2.5m
3.6m
AC cable CSA
2
4mm
(AWG10) ~ 10mm
Max. cable length (allowable
voltage drop: 0.5V)
4.3m
5.6m
Max. cable length (volt
drop: 0.5V, with min. CSA)
3.1m
4.6m
3.7m
5.8m
Max. cable length (volt drop:
Max. cable CSA
0.5V, with max. CSA)
2
4mm
AWG10
2
2.5mm
AWG10
2
(AWG6)
Max. cable
Max. cable length (volt
CSA
drop: 0.5V, with max. CSA)
2
16mm
AWG4
Max. cable length (volt drop:
Max. cable CSA
0.5V, with max. CSA)
2
6mm
AWG8
2
6mm
AWG8
5m
6.1m
4m
4.8m
6.9m
8.9m
7.5m
10.7m
15.1m
21.4m