Appendix A: Special Zone Operation

A.1 Overview
This section contains information for operating the control panel as detailed in the topics listed
below:
Section
A.2, "Releasing Zones (R0-R9)"
A.3, "Time, Date, and Holiday Functions"
A.4, "NAC Coding"
A.5, "Presignal and Positive Alarm
Sequence (PAS) Operation"
A.2 Releasing Zones (R0-R9)
A.2.1 Purpose of Releasing Zones
WARNING: When used for CO
!
in NFPA 12. Do not enter the protected space unless physical lockout and other safety
procedures are fully completed.
Do not use software disable functions in the panel as lockout.
The control panel provides ten Releasing Zones (R0-R9). These are special zones that you can use
for up to ten independent releasing operations. This section contains descriptions of each Releasing
Function option and an example of how Releasing Zone options work.
For instructions on programming Releasing Functions, refer to the NFS2-640 Programming
Manual.
Each Releasing Zone includes the following releasing options:
Option
Cross Zone
Delay Timer
Abort
Manual Release
Soak Timer
NFS2-640/E Operations Manual — P/N 52743:F1 06/16/2011
Special Zone
R0-R9
F5, F6, F7
F8
F0
releasing applications, observe proper precautions as stated
2
Description
Cross Zones let you program the control panel to activate a Releasing
Zone when two or more detectors are alarmed. Cross Zone selections are:
Y Two or more detectors are alarmed that are mapped to one of the ten
Releasing Zones (R0-R9)
Z Two or more detectors are alarmed that are mapped to two different
Software Zones and mapped to one of the ten Releasing Zones (R0-R9).
H At least one smoke detector mapped to one of the ten Releasing Zones
(R0-R9) is alarmed and at least one heat detector mapped to the same
Releasing Zone as the smoke detector is alarmed.
N Cross Zones not used
Select a 0–60 second delay before activating a zone.
An Abort Switch Type Code used to abort activation of a zone.
Allows immediate zone activation by overriding the abort function,
cross-zone function, and delay timer.
Automatically shuts off the releasing device after a preprogrammed period
of time. Select 0001-9999 seconds for a Soak Timer or 0000 seconds for
no Soak Timer.
Table A.1 Releasing Options
Refer to Page
page 49
page 52
page 54
page 55
49