Notifier NFS2-640/E Operation Manual page 71

Fire alarm control panel
Hide thumbs Also See for NFS2-640/E:
Table of Contents

Advertisement

System Troubles
TROUBLE MESSAGE
TROUBLE DESCRIPTION
TYPE
PROGRAM CORRUPTED
The database that houses the panel's programming is
corrupt.
PROGRAM MODE
A user is currently accessing the panel's programming
ACTIVATED
menus.
RELEASE DEV. DISABLE
Releasing devices have been disabled.
SELF TEST FAILED
Diagnostic test failed.
STYLE 6 POS. LOOP x
There is an open circuit on the positive side of loop x. Style 6 and Style 7 are supervised methods of
communicating with addressable devices. If the control panel detects a trouble (open), it will drive both ends of
the loop, maintaining communication in an unsupervised method. The latching trouble will display on the panel as
a Style 6 trouble until you correct the condition and press
of ISO-X isolator modules.
STYLE 6 NEG. LOOP x
There is an open circuit on the negative side of loop x. Style 6 and Style 7 are supervised methods of
communicating with addressable devices. If the control panel detects a trouble (open), it will drive both ends of
the loop, maintaining communication in an unsupervised method. The latching trouble will display on the panel as
a Style 6 trouble until you correct the condition and press
of ISO-X isolator modules.
STYLE 6 SHORT LOOP x
Style 6 and Style 7 are supervised methods of communicating with addressable devices. If the control panel
detects a trouble (open or short), it will drive both ends of the loop, maintaining communication in an
unsupervised method. The latching trouble will display on the panel as a Style 6 trouble until you correct the
condition and press
SYS INITIALIZATION
The devices are initializing.
TERM. SUPERVISORY
There is a communication error with the CRT-2.
UDACT NO ANSWER
The UDACT is not responding.
UDACT TROUBLE
The UDACT is in trouble.
* This trouble may be fire panel or backup battery related. Test and replace backup batteries if necessary/
NFS2-640/E Operations Manual — P/N 52743:F1 06/16/2011
SYSTEM TROUBLES
. Style 7 configuration of the SLC requires the use of ISO-X isolator modules.
RESET
Table D.2 System Troubles
Point and System Troubles Lists
ACTION
The database must be re-downloaded, or all
programming must be cleared and re-entered. If the
trouble still does not clear, contact Technical Services.
No action is required / Exit the Programming mode.
Enable the devices.
Call Technical Services.
. Style 7 configuration of the SLC requires the use
RESET
. Style 7 configuration of the SLC requires the use
RESET
No action is required, as the trouble will clear when
initialization is completed. However, devices will not
report off-normal events while this trouble exists.
Check connections to the CRT-2 terminal.
Determine whether the UDACT is functional, and
connected and addressed properly.
Determine if the UDACT is functional and wired
correctly.
71