Viewing and Printing a Read Status
An Annunciator Selection screen shows the information that will display on the ACS annunciators.
1 through 9
0
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
Annunciator addresses 1 to 19 can be programmed to any one of the above selections. If there is a UDACT,
selections A-M will be sent to Annunciator addresses 20 to 32 respectively.
The table above contains the ACS display selections. Annunciators set to annunciator address 1 to
19 can be programmed to any one of the above selections. If t here is a UDACT, selections A-M
will be sent to Annunciator addresses 20 to 32 respectively.
An example of ACS selections in Annunciator Selection Screen 1:
NOTE: An ACS selection marked with an asterisk (*) indicates no annunciator selection.
The figure above shows annunciator selections for addresses A1-A2 (addresses A3-A10, marked
with asterisks, are not selected).
Annunciators set to annunciator address 1 (A1) display the status of detectors 1-64 on SLC 1
(ACS Selection Group H)
Annunciators set to annunciator address 2 (A2) display the status of intelligent modules 1-64
on SLC-1 (ACS Selection Group C).
NFS2-640/E Operations Manual — P/N 52743:F1 06/16/2011
Programmable Annunciator #1 through #9
Programmable Annunciator #10
8 Systems points + Zones 1-56
Zones 57-99, 9 F zones, 8 R zones, 4NAC
Loop 1, Modules 1-64
Loop 2, Modules 1-64
Loop 1, Modules 65-128
Loop 2, Modules 65-128
Loop 1, Modules 129-159 & Loop 2, Modules 129-159
Loop 1, Detectors 1-64
Loop 2, Detectors 1-64
Loop 1, Detectors 65-128
Loop 2, Detectors 65-128
Loop 1, Detectors 129-159 & Loop 2, Detectors 129-159
Programmable for use with FireVoice NFV-25/50ZS
8 Systems points + Zones 1-56, used for remote station communicator (TM-4)
8 Systems points + Zones 1-56, used for municipal box trip output (TM-4)
Loop 1, Modules 65-100, Loop 1, Detectors 1-14 (Detector Maintenance
Reporting)
Loop 2, modules 65-100, Loop 2, Detectors 1-14 (Detector Maintenance
Reporting)
Loop 1, detectors 15-46 (Detector Maintenance Reporting)
Loop 2, Detectors 15-46 (Detector Maintenance Reporting)
Loop 1 Detectors 47-78 (Detector Maintenance Reporting)
Loop 2, Detectors 47-78 (Detector Maintenance Reporting)
Loop 1, Detectors 79-100 (Detector Maintenance Reporting)
Loop 2, Detectors 79-100 (Detector Maintenance Reporting)
Table 4.2 ACS Selection Groups (2 of 2)
A N N U N S E L E C T I O N :
A 5 = *
A 6 = *
A 7 = *
Figure 4.14 Annunciator Selection Screen 1 Example
A 1 = H A 2 = C A 3 = * A 4 = *
A 8 = *
A 9 = *
A 1 - = *
Read Status Operation
A 1 1 = *