Read Status Operation
How to View Read Status for a Releasing Zone (R0-R9)
Releasing
Zone Number
next device
previous device
Zone status (ON or OFF)
How to Read Status for System Functions
40
Figure 4.5 Sample Special Zone Read Status Display
From the "Read Status" screen, press 0, then press the
key. You can now view the Read Status of a Releasing Zone as
follows: press Z, enter the zone number (R0-R9), then press the
ENTER
R0, enter Z, enter R0, then press the
panel now displays information for a Releasing Zone as shown
below.
Zone label for Releasing Function
O F F R E L E A S E F U N C T
D E L A Y = 0 0
A B O R T = U L I C R O S S = N S O K = 0 0 0 0 R 0 0
Selections for
Releasing Zone R0
Figure 4.6 Sample Releasing Zone Read Status Display
The "System Functions" screen specifies global settings for the
control panel. From the "Read Status" screen, press 0, then press the
ENTER
follows: press Z, enter S0, press the
sample display and description of items for the Read Status of System
Functions:
S I L I N H = 0 0 0 A U T O = 0 0 0 V E R I F Y = 3 0 U S A T I M E
T E R M = N A C _ D L Y = Y L o c T B L I N K = 0 1 S T = 4 A C S = N
Parameter
Description
SIL INH=000
Silence Inhibit timer in
seconds. Required in
Canada and some areas of
the USA.
AUTO=000
Auto Silence Timer in
seconds.
VERIFY=30
Alarm Verification Timer
USA TIME
Time and date display
format
TERM=N
Terminal supervision
AC_DLY=N
Delays AC loss reporting
Table 4.1 System Function Parameters (1 of 2)
key. For example, to read the status of Releasing Zone
R E L E A S E C O N T R O L
Indicates Special Zone R0
key. You can now view Read Status for System Functions as
Settings
000 = no timer; or the timer duration in
seconds up to 300.
000 = no timer; 600-900 seconds.
00 = no timer; 00-30 seconds.
USA TIME or EUR TIME
YES – To supervise the wiring of an
FDU-80. 
NO – No FDU-80 supervision.
YES - AC loss reporting is delayed for
approximately 3 hours.
NO - No AC loss delay.
NFS2-640/E Operations Manual — P/N 52743:F1 06/16/2011
Viewing and Printing a Read Status
ENTER
key. The control
ENTER
key. Shown below is a
ENTER