Connecting the Pump to a SunTouch
The IntelliFloXF
RS-485 communication cable.
To connect the pump two wire RS-485 communication cable to the SunTouch circuit board:
1. Unlatch the front door of the SunTouch power center and open the door.
2. Loosen the retaining screw on front panel. Open the hinged front panel to access the
electronics compartment.
3. Route the two conductor cable up through the power center grommet opening located
on the left side, and up through the low voltage raceway to the motherboard.
4. Strip back the cable conductors 6 mm (1/4"). Insert the wires into the screw terminals
(provided). Secure the wires with the screws. Be sure to match the color coding of the
wires;
YELLOW to YELLOW and GREEN to GREEN.
5. Insert the connector on the COMPORT (J11) screw terminal on the SunTouch circuit board.
6. Close the control panel and secure it with the retaining screw.
7. Close the front door. Fasten the spring latch.
IntelliFloXF
and IntelliProXF
and IntelliProXF
pumps can be controlled by a SunTouch system via the
Switch OFF main system power to the SunTouch Power Center before making any connections.
Variable Speed Pump Installation and User's Guide
®
System
J11
COM PORT
RS-485 communication
cable (P/N 350122)
Pump
Drive
230 VAC Power to Pump
SunTouch Circuit Board