Generator Outputs - MULTIQUIP Power DCA85USJ2 Operation And Parts Manual

60hz generator (john deere 4045hf285 diesel engine)
Table of Contents

Advertisement

GENERATOR OUTPUT VOLTAGES
A wide range of voltages are available to supply voltage for
many different applications. Voltages are selected by using
the voltage selector switch (Figure 14). To obtain some of
the voltages as listed in Table 7 (see below) will require a
fi ne adjustment using the voltage regulator (VR) control
knob located on the control panel.
Voltage Selector Switch
The voltage selector switch (Figure 14) is located above
the output terminal panel's Hard Wire Hook-up Panel. It
has been provided for ease of voltage selection.
Figure 14. Voltage Change-Over Board
Voltage Selector Switch Locking Button
To lock the voltage selector switch, press and hold the
red button located at the bottom of the switch. While
holding the red button down, insert a pad lock into the hole
next to the button to retain it in the inward locked position.
When the lock is removed, the red button is spring loaded
and will return to its normal outward unlocked position
switch.
CAUTION
NEVER change the position of the voltage selector
switch while the engine is running. ALWAYS place
circuit breaker in the OFF position before selecting
voltage.
Table 7. Voltages Available
UVWO Output
Voltage Selector Switch
Terminal Lugs
3-Phase 240/139V Position
208V
3Ø Line-Line
1Ø Line-Neutral
120V
Voltage Selector Switch Single-Phase 240/120V Position
1Ø Line-Neutral/
120V
Line-Neutral
Line-Line
PAGE 42 — DCA85USJ2 60 HZ GENERATOR • OPERATION AND PARTS MANUAL — REV. #1 (03/22/11)
Voltage Selector Switch
3-Phase 480/270V Position
220V
240V
416V
440V
127V
139V
240V
254V
240V
N/A
N/A
N/A
Line-Line

GENERATOR OUTPUTS

Generator Amperage
Table 8 shows the maximum amps the generator can
provide. DO NOT exceed the maximum amps as listed..
Table 8. Generator Maximum Amps
Rated Voltage
Voltage Selector Switch
1Ø 240/120 position (120V)
Voltage Selector Switch
1Ø 240/120 position (240V)
Voltage Selector Switch
3Ø 240/139 position (240V)
Voltage Selector Switch
3Ø 480/277 position (480V)
GFCI Receptacle Load Capability
The load capability of the GFCI receptacles is directly
related to the voltage being supplied at either the output
terminals or the 2 twist lock auxiliary receptacles.
Tables 9 and 10 show what amount of current is available
at the GFCI receptacles when the output terminals and
twist lock receptacles are in use. Be careful that your load
does not to exceed the available current capability at the
receptacles.
Table 9. 1Ø GFCI Receptacle Load Capacity
Twist Lock (C6369)
Table 10. 3Ø GFCI Receptacle Load Capacity
(UVWO Terminals)
480V
277V
N/A
Maximum Amps
188.9 Amps (4 wire)
250 Amps x 2 (Zigzag)
94.4 Amps (4 wire)
KW in Use
Available Load
Current (Amps)
GFCI Duplex
1Ø 240/120V
5-20R 120V
60.0
0 amps/receptacle
58.8
5 amps/receptacle
57.6
10 amps/receptacle
56.4
15 amps/receptacle
55.2
20 amps/receptacle
KVA in Use
Available Load
Current (Amps)
GFCI Duplex
3Ø 240/480V
5-20R 120V
85
0 amps/receptacle
80.8
5 amps/receptacle
76.7
10 amps/receptacle
72.5
15 amps/receptacle
68.4
20 amps/receptacle
250A (Zigzag)
204 Amps
102 Amps