Output Terminal Panel Connections - MULTIQUIP WHISPERWATT DCA800SSK2 Operation And Parts Manual

Whisperwatt series 60hz generator (std.) (komatsu saa6d170e-3 diesel engine)
Table of Contents

Advertisement

UVWO TERMINAL OUTPUT VOLTAGES
Various output voltages can be obtained using the UVWO
output terminal lugs. The voltages at the terminals are
dependent on the placement of the jumpers plates (6)
on the Voltage ChangeOver Board (Figure 17) and the
adjustment of the Voltage Regulator Control Knob.
Remember the voltage changeover board determines the
range of the output voltage and can be confi gured in two
different positions that provide 6 different output voltages
at the UVWO output terminals. The generator is shipped
from the factory in the 240V confi guration. The voltage
regulator (VR) allows the user to increase or decrease the
selected voltage.
3Ø-240V UVWO Terminal Output Voltages
1.
Jumper the voltage changeover board for 240V
operation as shown in Figure 17.
Figure 17.
Voltage ChangeOver Board 240V
Confi guration
2.
Connect the load wires to the UVWO terminals as
shown in Figure 18.
Figure 18.
UVWO Terminal Lugs
DCA800SSK2 60 HZ GENERATOR • OPERATION AND PARTS MANUAL — REV. #0 (09/03/09) — PAGE 27

OUTPUT TERMINAL PANEL CONNECTIONS

3.
Turn the voltage regulator knob (Figure 19) clockwise
to increase voltage output, turn counterclockwise to
decrease voltage output. Use voltage regulator
adjustment knob whenever fi ne tuning of the output
voltage is required
Figure 19.
Voltage Regulator Knob
1Ø-240V UVWO Terminal Output Voltages
1.
Make sure the voltage changeover board is jumpered
for 240V operation as shown in Figure 17.
2.
Connect the load wires to the UVWO terminals as
shown in Figure 20.
Figure 20.
UVWO Terminal Lugs 1Ø240V
Connections
1Ø-120V UVWO Terminal Output Voltages
1.
Make sure the voltage changeover board is jumpered
for 240V operation as shown in Figure 17.
2.
Adjust voltage regulator knob (Figure 19) for an output
of 208V to obtain 120V at the UVWO terminals.
3.
Connect the load wires to the UVWO terminals as
shown in Figure 21.
Figure 21.
UVWO Terminal Lugs
Connections
1Ø139V

Advertisement

Table of Contents
loading