UVWO TERMINAL OUTPUT VOLTAGES
Various output voltages can be obtained using the UVWO
output terminal lugs. The voltages at the terminals are
dependent on the position of the Voltage Selector Switch
and the adjustment of the Voltage Regulator Control
Knob.
Remember the voltage selector switch determines the
range of the output voltage. The voltage regulator (VR)
allows the user to increase or decrease the selected
voltage.
3Ø-220/127 UVWO Terminal Output Voltages
1.
Place the voltage selector switch in the 3Ø 240/139
position as shown in Figure 18..
Figure 18.
Voltage Selector Switch
3Ø-240/139V Position
2.
Connect the load wires to the UVWO terminals as
shown in Figure 19.
Figure 19.
UVWO Terminal Lugs
3Ø-220/127V Connections
PAGE 28 — DCA45SSIU3 50 HZ GENERATOR • OPERATION AND PARTS MANUAL — REV. #2 (12/19/08)

OUTPUT TERMINAL PANEL CONNECTIONS

3.
Turn the voltage regulator knob (Figure 20) clockwise
to increase voltage output, turn counterclockwise to
decrease voltage output. Use voltage regulator
adjustment knob whenever fi ne tuning of the output
voltage is required.
Figure 20.
Voltage Regulator Knob
3Ø-200V/1Ø-115V UVWO Terminal Output Voltages
1.
Place the voltage selector switch in the 3Ø 240/139
position as shown in Figure 21.
Figure 21.
Voltage Selector Switch
3Ø-240/139V Position
2.
Connect the load wires to the UVWO terminals as
shown in Figure 22.
Figure 22.
UVWO Terminal Lugs
3Ø-200/1Ø-115V Connections Connections
NOTICE
To achieve a 3Ø 200V output the voltage selector switch
must be in the 3Ø-240/139 position and the voltage
regulator must be adjusted to 200V..