GENERATOR OUTPUT VOLTAGES
A wide range of voltages are available to supply voltage
for many different applications. Voltages are selected by
applying jumpers (6) to the voltage changeover board
(Figure 11). To obtain some of the voltages as listed in
Table 7 (see below) will require a fi ne adjustment using
the voltage regulator (VR) control knob located on the
control panel.
Voltage ChangeOver Board
The voltage changeover board (Figure 11) is located on
the control box, behind the generator control panel. This
board has been provided for ease of voltage selection.
Figure 11.
Voltage ChangeOver Board
CAUTION
NEVER attempt to place jumper plates on the voltage
changeover board while the generator is in operation.
There exist the possibility of electrocution, electrical
shock or burn, which can cause severe bodily harm
or even death!
Table 7.
Voltages Available
Three Phase
208V
220V
(Switchable)
Single Phase
120V
1127V
(Switchable)
DCA800SSK2 60 HZ GENERATOR • OPERATION AND PARTS MANUAL — REV. #0 (09/03/09) — PAGE 25
240V
416V
440V
480V
139V
240V
254V
277V

GENERATOR OUTPUTS

Generator Amperage
Table 8 shows the maximum amps the generator can
provide. DO NOT exceed the maximum amps as listed.
Table 8.
Generator Maximum Amps
Rated Voltage
1Ø 120 Volt
1Ø 240 Volt
3Ø 240 Volt
3Ø 480 Volt
Maximum Amps
1777.8 amps (4 wire)
888.9 amps (4 wire)
1924.6 amps
962.3 amps