Messages List - GE SG SERIES 10 Operating Manual

10, 20, 30 and 40 kva
Table of Contents

Advertisement

g
6.6.2

Messages list

Code
Message
WATCHDOG
4002
RESET
RECTIFIER
4111
UTILITY OK
BATTERY TEST
4119
STARTED
BATTERY TEST
4120
STOPPED
RECTIFIER
4161
ON
RECTIFIER
4162
OFF
GENERATOR
4163
ON
GENERATOR
4164
OFF
INVERTER
4302
CANNOT BE
TURNED ON
INVERTER
4303
CANNOT BE
TURNED OFF
INVERTER
4361
ON
INVERTER
4362
OFF
BYPASS UTILITY
4411
OK
COMMAND
4500
LOAD OFF
NO BYPASS
4521
POWER
MULTIPLE LOAD
4534
TRANSFER
OPM_SGS_USM_10K_40K_0US_V010.doc
The microprocessor has detected an incorrect operation:
Transfers the Load on Utility and performs a program reset.
The Inverter will restart automatically and will supply the
Load.
Rectifier Input Utility is again within the admitted tolerance
(voltage, frequency and phase).
Start of Manual or Automatic Battery Test.
End of Manual or Automatic Battery Test.
Rectifier started.
Rectifier shutdown.
Customer Interface (X1 - 11, 22) received a Gen-set ON
signal.
Operating mode depend on setting of Parameters.
Customer Interface (X1 - 11, 22) received a Gen-set OFF
signal.
Function Bypass enabled depends on setting of Parameter.
Inverter cannot be switched on because one of the following
conditions is still present:
Over Temperature
Low Battery Voltage
Inverter Fuses
Overload
K7 opening Failure
High Battery Voltage
DC Low
EPO
Inverter cannot be switched OFF, because the Load cannot
be switched to Utility (voltage out of tolerance, not synchrony,
BP blocked).
The command to start the Inverter has been activated on the
control panel.
The command to switch OFF the Inverter has been activated
by the control panel or automatically for alarm presence.
Bypass Input Utility is again within tolerance (voltage,
frequency and phase).
Disconnection of the Load by opening K6 and K7 for:
EPO / total off / Overload / stop operation.
With the Load supplied by Automatic Bypass, a Utility Failure
or K6 opening occurred.
2 transfers Inverter- Utility have been detected in a short time,
(default 30 sec.).
39/88
Meaning
Operating Manual SG Series 10, 20, 30 & 40 kVA
GE