7.4.7 Restore to normal operation after "total off"

View of the panel after pressing the button "total off".
All Contacts are open;
Rectifier, Inverter and Static-Switch shutdown.
First operated unit
1. Reset "total off" by pressing and holding the "total off" button and then the
"inverter on" ( I ) key, on any of the Units simultaneously, until Load is supplied
from Bypass and the Rectifiers start.
System output connects to Bypass Utility.
Rectifiers start with blinking LED.
At the end of Soft-start the LED's remains lit.
The LCD screen
First operated unit
2. Connect the Battery to all Units by closing the external Battery Switch(es) or
Fuses.
OPM_SGS_USM_10K_40K_0US_V010.doc
on all Units
shows: "LOAD ON BYPASS".
75/88
All other units of the system
All other units of the system
Operating Manual SG Series 10, 20, 30 & 40 kVA
GE
Continue