GE SG SERIES 10 Operating Manual page 38

10, 20, 30 and 40 kva
Table of Contents

Advertisement

g
Code
Alarms
BATTERY
4697
OVERTEMPERATURE
BATTERY POWER
4698
INSUFFICIENT
4700
DC LOW
LOAD LOCKED
4900
ON INVERTER
4955
OVERTEMPERATURE
LOAD OFF DUE TO
4998
EXTENT. OVERLOAD
LOAD OFF DUE
4999
TO UBATT. OR TEMP.
OPM_SGS_USM_10K_40K_0US_V010.doc
Detection of Battery over temperature condition.
Can be deactivated by Service.
In case of Utility Failure, with the actual Load, the run time
would be below stop operation time (default 3 minutes).
Battery voltage is at the lowest limit.
Will stay Off inverter until the battery voltage reaches the
value in parameter.
The Load is locked on Inverter after 3 Load transfers within 30
seconds.
After time out (default 30 sec.) Bypass will be free.
An over-temperature condition has been detected on Inverter.
Elapsed "stop operation" time, Inverter shutdown.
With Utility OK, Load is transferred on Utility.
Load Off after time-out of "stop operation" for overload on
Inverter or Bypass (time depending on the % of overload).
Load Off after time-out of "stop operation" with missing Utility
due to Battery low voltage or over-temperature condition.
38/88
Meaning
Operating Manual SG Series 10, 20, 30 & 40 kVA