Table 8 Compute enclosure 3-phase HP 2400 W power supply specifications (North America/Japan)
(continued)
Specification
Max input current per line cord
Input requirements
Rated input voltage
Rated input frequency
Maximum inrush current
Ground leakage current
Power factor correction
Table 9 Compute enclosure 3-phase HP 2400 W power supply specifications (International)
Specification
Power cords (4)
Max input current per line cord
Input requirements
Rated input voltage
Rated input frequency
Maximum inrush current
Ground leakage current
Power factor correction
Table 10 Compute enclosure power requirements
Power required (50–60 Hz)
User expected maximum power
1
Typical maximum Power or User expected maximum power (Input power at the ac input expressed in Watts and Volt-Amps.)
This figure was developed with the absolute maximum configuration running applications designed to draw the maximum
power possible. It is highly unlikely that any real-world application will result in this amount of power use for any significant
time period.
24
System specifications
1
Value
3.0m (10ft)
24.0 A at 200 VAC
23.1 A at 208 VAC
200 VAC to 240 VAC line-to-line 3–phase
50–60 Hz
100 A for 10 ms
3.5 mA
0.98
Value
IEC-309 220–240V, 5–pin, 16 A
3.0m (10ft)
12.1 A at 220 VAC
1 1.1 A at 240 VAC
200 VAC to 240 VAC line-to-neutral 3–phase
50-60 Hz
100 A for 10 ms
3.5 mA
0.98
Watts
8820
VA
9000