HP Integrity Superdome 2 utilizes variable speed fans to realize the most efficient use of air. The
volume of air required varies with the temperature of the air supplied to the inlet of HP Integrity
Superdome 2. The following table and chart illustrate the necessary volume of air to enable proper
operation.
IMPORTANT:
Equipment orientation will best be served in a parallel fashion to the air flow supply
and return. Supply air will flow down cold aisles which are parallel to equipment rows, and return
air to CRAC through parallel air flow. Perpendicular air flow causes too much room mixing, places
higher electrical loads on room, and can lead to unexpected equipment problems.
Table 15 Required airflow for inlet temperature
Inlet air temperature (°C)
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
Required airflow (CFM)
803
812
821
831
842
854
866
880
894
910
927
945
964
985
1007
1031
1057
1085