Factory Settings; Return To Factory Settings; Factory Values - Worcester 6 KW Instruction Manual

Worcester greenstore lecp ground source heat pump in either system or combi variants
Hide thumbs Also See for 6 KW:
Table of Contents

Advertisement

FACTORY SETTINGS

21.13.5 LOW TEMPERATURE COLLECTOR CIRCUIT OUT E2X.T11
Function: The information is given if the temperature of the collector
circuit out is too low. First, a information is given. If the information
appears several times during a certain time period, the warning
transforms into a category A alarm.
For settings of T11: (Chapter 20.9).
Alarm timer starts: Yes.
Reset condition: T11 exceeds the lowest permitted temperature T11
plus hysteresis.
Category: J which goes over into A.
21.13.6 HOT WATER PEAK FAILURE, NEW TRY WITHIN 24 HOURS
Function: The hot water has not come up at the right temperature. The
hot water peak is repeated at the same time on the next day.
Reset condition: The correct hot water peak temperature is reached.
Category: Z.
21.13.7 TEMPORARY HEAT PUMP STOP DUE TO WORKING AREA
LIMITS
Function: The information is displayed only if Hot gas stop function
activated has been set to Yes. The compressor stops until the hot gas
temperature falls below the set limit.
Reset condition: The hot gas temperature is within the range of the
compressor.
Category: Z.
22
FACTORY SETTINGS

22.1 RETURN TO FACTORY SETTINGS

The function exists on both customer and installer level. All settings
available to the customer are restored on customer level.
All settings on installer level are restored when the function is used on
installer level. Customer level settings are not affected.
Room temperature
Circuit 1 Heating
Type of heating system
Highest permitted flow temperature T1
Lowest permitted flow temperature T1
Heat curve
Heat curve hysteresis heat pump x
Room sensor (room controller)
Room temperature program
Table 174 Factory settings Room temperature
64
21.13.8 TEMPORARY HOT WATER STOP DUE TO WORKING AREA
LIMITS
Function: The information is displayed only if Hot gas stop function
activated has been set to Yes. Ongoing hot water operation is aborted
and replaced with heating operation.
Reset condition: The hot gas temperature is within the range of the
compressor.
Category: Z.
21.13.9 ADDITIONAL HEAT IS NOW WORKING AT ITS HIGHEST
TEMPERATURE
Function: The additional heat begins to be stepped down. The
information is activated in additional heat mode if the outgoing
temperature (T1 or T8) approaches the set maximum value. The
information is blocked during hot water peaks or extra hot water.
Reset condition: The information is deactivated when the temperature
falls.
Category: Z.
21.13.10 TEMPORARY HOT WATER STOP E2X
Function: Ongoing DHW mode is temporarily interrupted; the system
changes over to heating mode.
Reset condition: DHW temperature drops a few degrees.
Category: Z.

22.2 FACTORY VALUES

Access level 0 = Customer
Access level 1 = Installer
Maximum
Minimum
Time factor
Room temperature influence
Acknowledge room sensor (room controller)
Active program
View/edit active program
Room temperature normal
Temperature increase/decrease (no room controller)
Setting temp. increase/decrease (no room controller)
> Limit value for left or right end point
> Change when much colder/warmer
> Change when colder/warmer
Room temperature influence (no room controller)
Room temperature exception
Copy to all heating circuits
F value
Access level
Underfloor
1
80/45 °C
1
10 °C
1
0
25.0K
1
4.0K
1
20.0
1
3,0
1
(Auto)
1
HP optimized
0
0
20,0 °C
0
=
0
1
0,0 °C
1
8%
1
3%
1
3,0
0
17,0 °C
0
No
0
6 720 806 768 (2013/02)