>>> Room temperature during time program
Factory setting
Lowest value
Highest value
Table 51 Room temperature, exception
▶ Set the temperature that should apply as exceptional temperature in
the program.
The menu is displayed only if Program 1or Program 2has been
selected.
>>> Copy to all heating circuits
Factory setting
Alternative
Table 52 All circuits
▶ Select Yes to have the same control for all installed circuits.
The menu is displayed only under Circuit 1.
Room temperature program when there is no room controller:
>> Room temperature program
>>> Active program
>>> View/edit active program
The same as when there is a room controller, see above.
>>> Room temperature normal
Factory setting
Lowest value
Highest value
Table 53 Room temperature, normal
▶ Set the measured value in the room.
The indicated value is used by temperature programs to calculate the
difference between normal and exceptional temperature.
>>> Temperature increase/decrease
Factory setting
Alternative
Table 54 Room temperature increase/decrease
▶ Use this function to adjust the room temperature so that the normal
room temperature (see the previous menu) becomes the desired
temperature.
▶ Use this function to simply increase or decrease the heat when there
are no room controllers.
– – gives approx. 1 °C lower room temperature.
– gives approx. 0.5 °C lower room temperature.
+ gives approx. 0.5 °C higher room temperature.
++ gives approx. 1 °C higher room temperature.
>>> Setting temp. increase/decrease
>>>> Limit value for left or right end point
Factory setting
Lowest value
Highest value
Table 55 Heating increase/decrease limit value
▶ Set which outdoor temperature should be the limit value for the end
point that should be adjusted when increase/decrease is requested.
At outdoor temperatures lower than the limit value, the flow
temperature in the right end point (-35 °C) of the heat curve is
affected, with change indicated in %, see below.
At outdoor temperatures higher than the limit value, the flow
6 720 806 768 (2013/02)
17.0 °C
10.0 °C
30.0 °C
No
No/Yes
20.0 °C
10.0 °C
35.0 °C
=
– – , – , =, +, ++
0.0 °C
-10.0 °C
15.0 °C
temperature in the left end point (+20 °C) of the heat curve is
affected, with change indicated in %, see below.
>>>> Change when much colder/warmer
Factory setting
Lowest value
Highest value
Table 56 Change when much colder/warmer
▶ Set how much % the flow temperature in the applicable end point of
the heat curve should change down or up when – – or ++ is selected
in Temperature increase/decrease.
>>>> Change when colder/warmer
Factory setting
Lowest value
Highest value
Table 57 Change when colder/warmer
▶ Set how much % the flow temperature in the applicable end point of
the heat curve should change down or up when – or + is selected in
Temperature increase/decrease.
>>> Room temperature influence
Set in the same way as in menu Room sensor (room controller)
( Chapter 20.1). The setting is used in the temperature program to
calculate how the flow line temperature is affected when Room
temperature exception is to apply.
>>> Room temperature during time program
>>> Copy to all heating circuits
The same as when there is a room controller, see above.
It always takes some time for a change of a heating
setting, e.g. an increase or decrease in room
temperature, to apply. The same applies in the event of a
quick change of the outdoor temperature. This is why
you should always wait for at least 24 hours before
making a new change.
> Circuit 2, 3...
Make the settings for the first mixed circuit under Circuit 2. Other
circuits are displayed only if they exist. The same functions apply to
these as the functions for circuit 2.
>> Mixing valve mode
Factory setting
Alternative
Table 58 Mixing valve operating mode
▶ Select Off if the circuit is not ready or needs to be turned off
temporarily or should not be used.
>> Type of heating system
Factory setting
Alternative
Table 59 Type of heating system
▶ Select type of heating system.
The factory settings for the Radiator have a curve value (flow
temperature) of 22 °C at 20 °C an outdoor temperature, 37.4 °C at –
2.5 °C and 60 °C at -35 °C at an outdoor temperature (the high point of
the curve).
The factory settings for the Underfloor have a curve value (flow
temperature) of 22 °C at 20 °C outdoor temperature, 27.2 °C at -2.5°C
and 35 °C at -35 °C outdoor temperature.
SETTINGS
8%
1%
20%
3%
1%
20%
Off
Heating/Off
Underfloor
Radiator/Underfloor
45