Worcester 6 KW Instruction Manual page 44

Worcester greenstore lecp ground source heat pump in either system or combi variants
Hide thumbs Also See for 6 KW:
Table of Contents

Advertisement

SETTINGS
>> Heat curve hysteresis heat pump x
>>> Maximum
F value
Lowest value
Highest value
Table 43 Maximum hysteresis
▶ Set how big the maximum hysteresis for the flow temperature can be.
>>> Minimum
Factory setting
Lowest value
Highest value
Table 44 Minimum hysteresis
▶ Set how big the minimum hysteresis for the flow temperature can be.
>>> Time factor
Factory setting
Lowest value
Highest value
Table 45 Time factor
▶ Select how long the compressor should be on or off in heating mode.
Higher set values result in fewer compressor starts and stops, which
achieves higher economy. However, more pronounced temperature
fluctuations in the heating system may result than with lower values.
>> Room sensor (room controller)
> Room temperature influence
Factory setting
Lowest value
Highest value
Table 46 Room temperature influence
▶ Set how much a 1 K ( °C) difference in room temperature should
influence the set point value for the flow temperature.
Example: at a 2 K ( °C) deviation from the set room temperature, the
set point value for the flow temperature is changed by 6 K ( °C) (2 K
deviation * factor 3 = 6 K).
The menu is displayed only if a room controller is installed.
>>> Acknowledge room sensor (room controller)
Factory setting
Alternative
Table 47 Acknowledge room controller
▶ Indicate No only if the room controller, even if it is installed, should not
be used.
>> Room temperature program
Factory setting
Alternative
Table 48 Program selection, circuit 1
▶ Choose if the circuit should be controlled with a program or not.
Optimised operation
This means that the control unit is only controlled by the flow set point
value ( Chapter 20.1.1), without programmed changes during the
day. Optimised operation provides the best comfort and energy savings
in the vast majority of cases.
44
25.0K
The value in Minimum
30.0K
4.0K
2.0K
The value in Maximum
20.0
1.0
30.0
3.0
0.0
10.0
Yes (if correctly installed)
Yes/No
HP optimized
• HP optimized
• Program 1
• Program 2
Program 1 and 2
These selections provide an opportunity to define user programs for
time control by adjusting the start and stop times, as well as a normal and
an programmed temperature.
Program
Day
Program 1, 2
Mon - Sun
Table 49 Program 1 and 2
To set the desired time of day:
▶ Select Program 1 or Program 2.
▶ Go to menu View/edit active program.
▶ Select day by turning the menu dial.
Fig. 53
▶ Press the menu dial to highlight the value to be changed.
Fig. 54
▶ Turn the menu dial until the desired setting has been selected.
▶ Then press the menu dial.
▶ Turn the menu dial to be able to set additional values in the same way
as above.
▶ Go back one step with
.
▶ Select Saving alternative:
– Return without saving
– Program 1
– Program 2
The set changes are saved as a selected program or not at all.
▶ To adjust the normal temperature, proceed to menu Room
temperature normal.
▶ To adjust the exceptional temperature, proceed to menu Room
temperature exception.
Room temperature program when there is a room controller:
>> Room temperature program
>>> Active program
If a program is selected, the following (if the menu button is turned) is
displayed:
>>> View/edit active program
>>> Room temperature normal
Factory setting
Lowest value
Highest value
Table 50 Room temperature, normal
▶ Set the desired set point for the room temperature.
Start
Stop
5:30
22:00
6 720 643 415-13.1I
6 720 643 415-14.1I
20.0 °C
10.0 °C
35.0 °C
6 720 806 768 (2013/02)