Additional Heat - Worcester 6 KW Instruction Manual

Worcester greenstore lecp ground source heat pump in either system or combi variants
Hide thumbs Also See for 6 KW:
Table of Contents

Advertisement

>> Heat source
Factory setting
Alternative
Table 134 Heat source drying
>> Program settings
>>> Flow temperature increase per heating step
Factory setting
Lowest value
Highest value
Table 135 Temperature increase per heating step
>>> Number of days per heating step
Factory setting
Lowest value
Highest value
Table 136 Days per heating step
>>> Maximum flow temperature
Factory setting
Lowest value
Highest value
Table 137 Maximum flow temperature drying
>>> Number of days with maximum temperature
Factory setting
Lowest value
Highest value
Table 138 Days with maximum temperature
>>> Flow temperature decrease per cooling step
Factory setting
Lowest value
Highest value
Table 139 Temperature decrease per cooling step
>>> Number of days per cooling step
Factory setting
Lowest value
Highest value
Table 140 Days per cooling step
CAUTION: Risk of floor damage
▶ Follow the manufacturer's recommendations for the
floor tiles.
6 720 806 768 (2013/02)

Additional heat

Both/Compressor/Additional heat
5.0K
1.0K
10.0K
1
1
5
45 °C
25 °C
60 °C
4
0
20
5.0K
1.0K
10.0K
1
1
5
20.8 ADDITIONAL HEAT
The additional heat works together with the heat pump to maintain the
right heating in the circuits. The additional heat can be selected to work
alone.
See manual for the multi-module for the mixed additional
heat operating mode.
Under Additional heat, there are:
• Additional heat general
• Electric additional heat
• Hot water electric heater
• Additional heat program
> Additional heat general
Under Additional heat general the functions that are common to
electric additional heat and mixed additional heat are found.
>> Start delay
Factory setting
Lowest value
Highest value
Table 141 Additional heat start delay
▶ Set what start delay should apply to the additional heat.
When the need for additional heat arises, a timer with set time is
started. When this time has passed the additional heat starts.
>> Additional heat only
Factory setting
Alternative
Table 142 Additional heat only
▶ Change to Yes if the additional heat should work alone.
This can be suitable if the heat pump should provide heat before, e.g.,
the collector circuit is ready.
>> Block additional heat
Factory setting
Alternative
Table 143 Block additional heat
▶ Indicate if the additional heat should be blocked. In this case, the
additional heat may not take part. The additional heat is, however,
allowed to kick in in alarm mode and additional heat only mode if no
other blocking function is enabled.
>> Maximum outdoor temperature for additional heat
Factory setting
Lowest value
Highest value
Table 144 Maximum outdoor temperature for additional heat
▶ Set the desired temperature limit. If the outdoor temperature exceeds
this value, the additional heat may not work.
> Electric additional heat
The control unit supports 1 additional heat unit.
The settings for connection capacity and regulator for the additional
heat use are made under this menu.
> Electric heater connection
>> Connected output
▶ Shows the actual output of the input electric additional heat.
SETTINGS
120min
0min
240min
No
Yes/No
No
Yes/No
10 °C
-30 °C
40 °C
55