Bosch ICP-CC404 Installation Manual page 67

Hide thumbs Also See for ICP-CC404:
Table of Contents

Advertisement

1,12
Codepad Tamper – Access Denied
This output operates when the wrong code is entered
more times than allowed. The number of incorrect
attempts allowed is programmed in Location 356
(refer to Section 15.19 System Status – Access Denied on
page 63). This output resets when a valid User Code
is entered.
1,14
Horn Speaker (Output 1 Only)
This output operates only on Output 1. Use this
output for one or two 8 Ω horn speakers. Refer to
Section 17.9 Siren Run Time on page 71 and Section
17.10 Siren Sound Rate on page 71 to program the
speaker.
To enable monitoring of the horn speaker, select
Option 2 in Location 424 (refer to Section 18.1 System
Options 1 on page 73).
1,15
Sirens Running
This output operates for the duration of the Siren Run
Time programmed in Location 411 (refer to Section
17.9 Siren Run Time on page 71). When the sirens are
activated, this output resets when the Siren Run Time
expires. The relay output (Output 4) is set by default
for this operation.
2,0
Strobe Operating
This output operates when an alarm occurs and resets
when a valid User Code is entered. The strobe output
(Output 3) is set by default for strobe operation and is
programmed to reset automatically after 8 hours.
2,1
Silent Alarm
This output operates when any zone programmed to
activate silently. The output resets when the Siren
Run Time expires, an audible alarm is activated, or a
valid User Code is entered.
2,2
Alarm When in STAY Mode
This output operates when an audible or silent alarm
zone is activated when the system is armed in STAY
Mode 1 or STAY Mode 2. The output resets when
the system is disarmed.
2,3
Alarm When in AWAY Mode
This output operates when an audible or silent zone
alarm is activated when the system is armed in
AWAY Mode. The output resets when the system is
disarmed.
2,4
Mimic System Fault
This output operates without any time delays when
any system fault occurs, including an AC mains
supply failure. The output resets when the system
fault or the AC mains supply is restored.
2,5
Fire Alarm Resetting
This output operates when a 24-Hour Fire Zone is
activated. The output resets when a valid User Code
is entered or when Siren Run Time expires.
Bosch Security Systems, Inc. | 12/08 | F01U089401-02
ICP-CC404 | Installation Guide | 16.0 Programmable Outputs
2,6
Fire Alarm Latching
This output operates when a 24-Hour Fire Zone is
activated and resets when the system is armed or
disarmed.
2,7
Fire Alarm Verification
This feature is used on some commercial fire control
panels to reduce false alarms from smoke detectors. It
is very similar to zone pulse count used in some
motion detectors. A fire zone is allotted a pulse count
of 3 pulses over a period of 3 min.
If the smoke detector activates, the voltage to the
smoke detector is disconnected for 15 sec and then
reapplied. No alarm is registered.
If the unit activates again within 3 min of the first
activation, no alarm is registered and the voltage to
the smoke detector is again disconnected for 15 sec
and then reapplied.
If a third activation is detected within 3 min of the
first activation, (three pulses in 3 min) a fire alarm is
registered. Power to the smoke detector is maintained
to facilitate unit identification through the detector
memory.
Connect this output to the negative side of any fire or
smoke detector. To configure an output for this
feature, use these settings.
EVENT TYPE = 2,7
POLARITY = 10
TIMEBASE = 2
MULTIPLIER = 15
Program the zone to which the fire or smoke detector
is connected as:
ZONE TYPE = 13
ZONE PULSE COUNT = 3
ZONE PULSE COUNT TIME = 15
2,8
Remote Control 1
2,9
Remote Control 2
2,10
Remote Control 3
These outputs can be remotely activated (turned on
or off) by the following methods:
Remote codepad (refer to Section 6.2.6 Turning
Outputs On/Off on page 36 for more information).
Remotely through the Alarm Link Software (refer
to your Alarm Link Instruction Manual for more
information).
2,11
Radio Control Output 1
This output operates when the [DOOR] button on the
four-channel hand-held transmitter is activated.
2,12
Radio Control Output 2
This output operates when the [AUX] button on the
four-channel hand-held transmitter is activated.
67