Air For Combustion; Direct Outside Air For Combustion - Space-Ray Infrared Radiant Tube Heater PTS Series Installation And Operation Instructions Manual

Infrared radiant tube heater single stage push through system (positive pressure)
Table of Contents

Advertisement

INDIRECT VENTING
B.
products of combustion and provide fresh air for efficient combustion. Where unvented heaters are used, gravity
or mechanical means shall be provided to supply and exhaust at least 4 CFM per 1,000 Btu/hr input of installed
heaters. Exhaust vents must be located at the highest point above and in the vicinity of the heaters, and the inlet
vents must be located below the level of the heaters. An exhaust hood (Part #42924000) must be placed on the
flue adapter collar located on the end of the last body section when used unvented and must be mounted only in
an downward position as shown.
17.0)

AIR FOR COMBUSTION

If indoor combustion air is to be supplied for a tightly enclosed area, one square inch of free area opening shall be
provided below the heater for each 1,000 Btu/hr of heater input. Adequate clearances around the air inlet screen
must be maintained at all times. In larger open areas of buildings, infiltration normally is adequate to provide air for
combustion.
17.1)

DIRECT OUTSIDE AIR FOR COMBUSTION

Outside combustion air should be supplied directly to the heater when the building is subject to negative pressure, or
when contaminants or high humidity are present in the building air. These contaminants include paints, solvents,
corrosive vapors or any other foreign particles that may cause damage to the heater or result in poor combustion.
Outside combustion air can be brought directly to the heater by a 4" diameter duct less than 50 ft. long or equivalent
(see table in Section 16). This is attached to the 4" diameter starting collar (supplied with heater). The starting collar
is fitted to the rear of the burner box cabinet as shown below. An approved vent cap must be placed directly on the
end of the outside combustion air inlet pipe. The combustion air inlet should be not less than 3 ft. (0.9m), either
vertically or horizontally, from the flue vent termination. The air intake terminal must be located not less than 1 ft.
(30cm) above grade. It is good installation practice to supply combustion air from the same pressure zone as the
vent outlet. Avoid bringing combustion air to the heater from an attic space. There is no guarantee that adequate
combustion air will be supplied.
If the heater is installed less than 2 ft. from the ceiling, a combustion air inlet kit PN 44129510 must be provided to
allow for expansion/contraction of straight tube heaters (PTS series).
In colder climates, where necessary, insulate the outside combustion air duct. In high humidity applications, the
burner box should be sealed with silicone sealer.
(UNVENTED HEATERS) — This heater requires ventilation in the building to dilute the
–38–
Form #43343330
May 08

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents

Save PDF