Venting - Space-Ray Infrared Radiant Tube Heater PTS Series Installation And Operation Instructions Manual

Infrared radiant tube heater single stage push through system (positive pressure)
Table of Contents

Advertisement

D. LOW VOLTAGE (24V) THERMOSTAT CONNECTIONS – MULTIPLE HEATERS (utilizing a fan center relay)
16.0)

VENTING

A. BASIC FLUE VENTING — Venting must comply with the latest edition of the National Fuel Gas Code (ANSI
Z223.1-latest edition) or the authority having jurisdiction. Other venting references are in the equipment volume of
the ASHRAE Handbook.
Model
Heat
exchanger
length ft
PTS/U 40
20
PTS/U 50
20
PTS/U 50
30
PTS/U 75
20
PTS/U 75
30
PTS/U 100
30
PTS/U 100
40
PTS/U 125
30
PTS/U 125
40
PTS/U 125
50
PTS/U 150
40
PTS/U 150
50
PTS/U 150
60
PTS/U 175
50
PTS/U 175
60
PTS/U 175
70
PTS/U 200
50
PTS/U 200
60
PTS/U 200
70
Vent lengths shown in the table are for horizontal and vertical venting. If a longer length of vertical or horizontal
venting is required contact the manufacturer for assistance with vent sizing.
Maximum vent length ft.
(4" diameter)
45
45
35
45
35
45
35
60
50
40
60
50
40
60
50
40
60
50
40
–34–
Maximum Fresh air
intake length ft (4"
diameter)
50
50
40
50
40
50
40
50
40
30
50
40
30
50
40
30
40
30
30
Max. combination of
fresh air and vent ft. (4"
diameter)
75
75
65
75
65
75
65
75
65
55
75
65
55
75
65
55
65
55
45
Form #43343330