Table 2. Effective occupancy arbitration for Tracer MP580/581 with operator display (Continued)
Commun-
Manual
icated
override
1
schedule
(nviOccMan
(nviOcc
Cmd)
Schedule)
Null
Occupied
Unoccupied
Standby
Null
1
This value is the last enumeration received. It can come from either the nviOccManCmd network variable or the operator dis-
play schedule override.
2
The variable nviOccSensor is used with the SCC profile only. Refer to the Null rows in this column for the DAC profile.
3
This value represents whether or not the bypass timer is at zero or not. When a bypass request is made, the timer is set to the
value specified in the Occupied Bypass Timer field, and it begins to count down. While it is counting down, the value is not
zero. When the count down is complete, the value is zero.
CNT-SVP01C-EN
Controlling the occupancy mode of the Tracer MP580/581
Occupancy
Local
sensor
schedule
(nviOcc
Sensor
)
2
—
Occupied
Unoccupied
Null
—
—
—
—
Occupied
Occupied
Unoccupied
Null
Unoccupied
—
Null
Occupied
Unoccupied
Null
Local
Bypass
occupancy
timer
binary input
—
—
—
zero
not zero
Occupied
—
Unoccupied
zero
not zero
Not present
—
—
zero
not zero
—
zero
not zero
—
—
—
zero
not zero
Occupied
—
Unoccupied
zero
not zero
Not present
—
—
zero
not zero
—
—
—
zero
not zero
Occupied
—
Unoccupied
zero
not zero
Not present
—
Result
(nvoEffect
3
Occup)
Occupied
Standby
Bypass
Occupied
Standby
Bypass
Occupied
Unoccupied
Bypass
Standby
Bypass
Occupied
Standby
Bypass
Occupied
Standby
Bypass
Occupied
Unoccupied
Bypass
Occupied
Unoccupied
Bypass
Occupied
Unoccupied
Bypass
Occupied
63