Chapter 3 Configuring the Tracer MP580/581
46
1. In the Active Device View, click the Configuration button. The Config-
uration dialog box appears.
2. Click the DAC tab. The DAC configuration information appears
(Figure 33).
Note:
This tab is available only when the DAC profile is active in the
Tracer MP580/581.
Figure 33. Device configuration DAC tab
3. Under Units, click the display units option for the DAC profile config-
uration data.
4. Under Default Setpoints, type the heating and cooling default set-
points for the occupied, unoccupied, and standby modes.
Note:
You need to address only those fields that are used in the pro-
gram to control the air-handling unit.
5. Under Discharge Air Setpoints, type the discharge air setpoints for
the DAC profile.
6. Under Static Pressure, type the duct static pressure setpoint and
limit and the building static pressure setpoint.
CNT-SVP01C-EN