CNT-SVP01C-EN
Figure 20. Device configuration analog input
6. In the Type list, click the input type.
Note:
Only the first four universal inputs (Input 01 to Input 04) can
be configured as a Balco or platinum resistance temperature
detector (RTD). Only the first two universal inputs on each EX2
expansion module can be configured as Balco or platinum
RTDs.
7. In the Units list, click the units associated with the input.
8. In the Decimal Places list, click the number of digits you want to
appear to the right of the decimal when displaying the input value.
Determine how many digits appear to the right of the decimal in the
Rover Active Device View and on the Tracer MP580/581 operator dis-
play. Use the resolution of the sensor to determine the number of dec-
imal places. For example, if a temperature sensor is accurate to 0.1°F,
do not display more than one decimal place. However, a differential
pressure sensor input may need to display two or three decimal
places.
Configuring inputs
25