Chapter 8 Using the Occupancy and PID blocks
Figure 68. All occupancy modes setpoint adjustment
96
The DeEnumerator block turns on the appropriate pair of Switch blocks,
depending on the Occupancy block output. If a Switch block pair is off, it
contributes zero to the final cooling and heating setpoint calculation. If a
Switch block pair is on, it contributes the non-zero values to the final cool-
ing and heating setpoint calculation.
Note:
The occupied and occupied bypass setpoints are the same.
Occupied bypass should be considered an occupied mode.