Table of Contents

Advertisement

CNT-SVP01C-EN
4. If you want to change the input name, highlight the text and type a
new name.
Use a descriptive name because it appears in custom displays and
programs.
5. Under Type, click the Pulse option. The pulse input configuration
information appears (Figure 21).
Figure 21. Device configuration pulse input
6. In the Units list, click the units associated with the input.
7. In the Pulse Weight field, type the value per contact closure from the
meter.
8. Complete one of the following options:
Click another input name in the Name list to edit another input.
Click another tab to set up another item.
Click the Download button to send your changes to the Tracer
MP580/581. (If the Security Logon dialog box appears, log on.)
Click Close to close the Configuration dialog box.