Figure 67. Occupied and unoccupied mode setpoint adjustment
CNT-SVP01C-EN
Note:
You could use another Switch block to pick which setpoint is
used. That Switch block would be controlled by the heating or
cooling mode.
The program in Figure 68 on page 96 is a direct extension of the one
shown in Figure 67. Because it is sending setpoint values based on four
possible modes, it is more complex than the examples seen previously.
Each mode controls the cooling and heating setpoints to the values in
Table 7.
Table 7. Occupancy mode heating and cooling setpoint values
Mode name
Cooling setpoint
Occupied
Unoccupied
Occupied bypass
Occupied standby
Using the Occupancy block
Heating setpoint
74.0°F
71.0°F
85.0°F
65.0°F
74.0°F
71.0°F
78.0°F
69.0°F
95