Trane Tracer MP580 Programming Manual page 61

Programmable controller
Hide thumbs Also See for Tracer MP580:
Table of Contents

Advertisement

Figure 36. Start and stop time examples
CNT-SVP01C-EN
the daily schedules. Another set of Start and Stop rows appears in the
daily schedule table.
Note:
The controller does not check event order. It always implements
the last commanded mode. This implies that you could have two
starts or two stops in a row in a single day. Figure 36 illustrates
some examples of event orders. For Example 3, assume that the
previous day ended with a start event. Example 4 shows the
schedule output in the case of two start and stop events in a
row. The second event of the same type is ignored.
4. In the daily schedule table, click in the cell for the day-of-the-week
start time.
5. Type the time you want the occupancy to start.
Setting up the daily schedule