Storage Environment; Mounting Location - Trane Engineered Smoke Control System Application Manual

For tracer summit
Table of Contents

Advertisement

Chapter 6 Installing the EX2 expansion module
9 in.
(229 mm)
2 in.
(51 mm)
10.37 in.
24 in.
(263 mm)
(610 mm)
width with
cover
Clearances
Dimensions
86
Figure 44. Dimensions and clearances for metal-enclosure EX2
1 in.
(25 mm)
2 in.
(51 mm)
(25 mm)
2.25 in.
1 in.
(58 mm)
(25 mm)

Storage environment

The storage environment must meet the following requirements:
Temperature: From –40°F to 185°F (–40°C to 85°C)
Relative humidity: 5–93%, non-condensing

Mounting location

Trane recommends locating the EX2 module:
In an environment protected from the elements
Where public access is restricted to minimize the possibility of tam-
pering or vandalism
Near the controlled equipment to reduce wiring costs
Where it is easily accessible for service personnel
In conduit, in the same room, and no more than 20 ft (6.1 m) from the
FACP
1.875 in.
(48 mm)
(165 mm)
7 in.
(178 mm)
1 in.
(260 mm)
width without cover
6.5 in.
(229 mm)
10.25 in.
BAS-APG001-EN
0.28 in.
(7 mm)
9 in.