BAS-APG001-EN
3. At the last controller on the LonTalk link:
Connect the white wire to the first LonTalk screw terminal.
Connect the black wire to the second LonTalk screw terminal.
Place a 105 Ω termination resistor across the LonTalk screw
terminals.
Figure 38. Wiring the next device to the LonTalk connection on the
termination board
Wiring LonTalk to the Tracer MP581
75