Wiring Inputs And Outputs; Input/Output Wiring Guidelines - Trane Engineered Smoke Control System Application Manual

For tracer summit
Table of Contents

Advertisement

Chapter 5 Installing the Tracer MP581 programmable controller
64

Wiring inputs and outputs

The Tracer MP581 enclosure is designed to simplify the wiring and con-
figuration of inputs and outputs by providing a large space for routing
wires and by eliminating the need to manipulate jumpers. Table 16 lists
Tracer MP581 inputs and outputs.
Table 16. Inputs and outputs
Type
Number
Universal inputs
12
Static pressure
1
input
Binary outputs
6
Analog outputs
6

Input/output wiring guidelines

Input/output wiring must meet the following guidelines:
Wiring must conform with the National Electrical Code and local elec-
trical codes.
Use only 18 AWG twisted-pair wire with stranded, tinned-copper con-
ductors.
Binary input/output wires must not exceed 1,000 ft (300 m).
Analog input wires must not exceed 300 ft (100 m) for thermistors
and 0–10 Vdc inputs and 1,000 ft (300 m) for 0–20 mA inputs.
Analog output wires must not exceed 1,000 ft (300 m) for 0–10 Vdc
outputs and 0–20 mA outputs.
Do not run input/output wires in the same wire bundle with high-
voltage power wires. Running input/output wires with 24 Vac power
wires is acceptable, but the input wire must be shielded.
Terminate input/output wires before installing the main circuit board
(see "Installing the circuit board" on page 76).
Description
Dry-contact binary, thermistor,
0–20 mA, 0–10 Vdc, linear resistance.
The first four inputs can be used
directly with resistance temperature
detectors (RTDs).
Differential pressure sensor, 5 Vdc,
0–5 in. wc
Powered relay contacts, 6 VA at 24 Vac
0–10 Vdc or 0–20 mA
BAS-APG001-EN