Uukl Binding List (Smoke Alarm Status) - Trane Engineered Smoke Control System Application Manual

For tracer summit
Table of Contents

Advertisement

Chapter 8 Network variable bindings
Table 32. Smoke alarm custom bindings
Function
Smoke alarm any
smokeAlarmFloor01
smokeAlarmFloor02
smokeAlarmFloor03
smokeAlarmFloor04
supplyDuctSmokeDetect
returnDuctSmokeDetect
stairDuctSmokeDetect
stairShaftSmokeDetect
smokeFloorAlarm
126

UUKL binding list (smoke alarm status)

Table 32 shows an example list of smoke alarm custom bindings. In order
to comply with UL-864 annunciation and control requirements, smoke
alarm signals are sent to the mechanical system, FSCP lamps, and audio
alarms (Sonalerts). Smoke alarms specific to a zone are broadcast to
annunciate smoke alarms regardless of control sequence. A general
smoke alarm is broadcast to signal a switch from HVAC control mode to a
smoke control mode. Floor alarms are sent as an analog value to comply
with the subsequent alarms requirement.
Originator
Network variable
MP580-2
nvoSwitch02
nvoSwitch02
nvoSwitch02
MP580-2
nvoSwitch05
nvoSwitch05
MP580-2
nvoSwitch06
nvoSwitch06
MP580-2
nvoSwitch07
nvoSwitch07
MP580-2
nvoSwitch08
nvoSwitch08
MP580-2
nvoSwitch09
nvoSwitch09
MP580-2
nvoSwitch10
nvoSwitch10
MP580-2
nvoSwitch11
nvoSwitch11
MP580-2
nvoSwitch12
MP580-2
nvoPercent20
nvoPercent20
nvoPercent20
Destination
Mechanical system /nviSwitch37
MP580-3/nviSwitch37
MP580-4/nviSwitch37
Mechanical system /nviSwitch20
MP580-3/nviSwitch09
Mechanical system/nviSwitch21
MP580-3/nviSwitch12
Mechanical system/nviSwitch22
MP580-4/nviSwitch08
Mechanical system/nviSwitch23
MP580-4/nviSwitch11
Mechanical system/nviSwitch30
MP580-3/nviSwitch06
Mechanical system/nviSwitch31
MP580-4/nviSwitch05
Mechanical system/nviSwitch32
MP580-4/nviSwitch01
Mechanical system/nviSwitch33
Mechanical system/nviPercent20
MP580-3/nviPercent20
MP580-4/nviPercent20
BAS-APG001-EN