Chapter 2 Pre-installation considerations
28
Table 5. Sample automatic smoke control matrix (dedicated)
Equipment
Zone 1
Main sup fan
On
Main R/E fan
On
Stair press fan
On
1st flr sup dmpr
Close
1st flr ret dmpr
Open
2nd flr sup dmpr
Open
2nd flr ret dmpr
Close
3rd flr sup dmpr
Close
3rd flr ret dmpr
Close
4th flr sup dmpr
Close
4th flr ret dmpr
Close
Smoke zone 1
Alarm
Smoke zone 2
Adjacent
Smoke zone 3
Unaffected
Smoke zone 4
Unaffected
Table 6. Sample automatic smoke control matrix (nondedicated)
Equipment
Zone 1
Main sup fan
On
Main R/E fan
On
Stair press fan
On
1st flr sup dmpr
Open
1st flr ret dmpr
Open
2nd flr sup dmpr
Open
2nd flr ret dmpr
Open
3rd flr sup dmpr
Open
3rd flr ret dmpr
Open
4th flr sup dmpr
Open
4th flr ret dmpr
Open
Smoke zone 1
Alarm
Smoke zone 2
Adjacent
Smoke zone 3
Open
Smoke zone 4
Open
First smoke zone in alarm
Zone 2
Zone 3
On
On
On
On
On
On
Open
Close
Close
Close
Close
Open
Open
Close
Open
Close
Close
Open
Close
Open
Close
Close
Adjacent
Unaffected
Alarm
Adjacent
Adjacent
Alarm
Unaffected
Adjacent
First smoke zone in alarm
Zone 2
Zone 3
On
On
On
On
On
On
Open
Open
Open
Open
Open
Open
Open
Open
Open
Open
Open
Open
Open
Open
Open
Open
Adjacent
Open
Alarm
Adjacent
Adjacent
Alarm
Open
Adjacent
Zone 4
On
On
On
Close
Close
Close
Close
Open
Close
Close
Open
Unaffected
Unaffected
Adjacent
Alarm
Zone 4
On
On
On
Open
Open
Open
Open
Open
Open
Open
Open
Open
Open
Adjacent
Alarm
BAS-APG001-EN