Chapter 8 Network variable bindings
Table 31. Watchdog communication alarm custom bindings
Function
Communication check from hub
multi-vibrator
Communication check to hub
multi-vibrator
Communication check to hub:
FSCP unit multi-vibrator
BMTX/EX2 communication
check
BMTX/EX2 communication
check to FSCP unit comm. status
124
In Table 31, the term multi-vibrator is used to indicate a network
variable whose state is changed regularly. The receiver expects this value
to change state within a certain interval. If it does not, a communication
fault is generated. The term comm. status is used to indicate a network
variable whose state is dependent on that particular MP581's EX2 and
BMTX communication status. If either are down, a communication fault
is generated.
Originator
MP580-2
nvoSwitch36
nvoSwitch36
nvoSwitch36
Mechanical system
nvoSwitch38
MP580-3
nvoSwitch38
MP580-4
nvoSwitch38
Mechanical system
nvoSwitch39
MP580-3
nvoSwitch39
MP580-4
nvoSwitch39
Network
variable
Mechanical system/nviSwitch38
MP580-3/nviSwitch38
MP580-4/nviSwitch38
MP580-2/nviSwitch34
MP580-2/nviSwitch35
MP580-2/nviSwitch36
MP580-2/nviSwitch37
MP580-2/nviSwitch38
MP580-2/nviSwitch39
Destination
BAS-APG001-EN