Trane Engineered Smoke Control System Application Manual page 114

For tracer summit
Table of Contents

Advertisement

Chapter 7 Programming
102
The wireless connector, smokeAlarmFloor, is used for the following two
reasons:
Because smokeAlarmFloor clears the floor alarms value one program
execution sooner than when using just the binary variable, smoke
AlarmAllFloor
To send a smoke alarm to any floor (see Figure 54 on page 103).
The relevant floor smoke alarm is communicated to the smoke control
panel and mechanical system via a custom binding.
Figure 53. Subsequent alarms—First reaction
BAS-APG001-EN