Chapter 5 Installing the Tracer MP581 programmable controller
54

Specifications

The Tracer MP581 conforms to the specifications shown in Table 13.
Table 13. Tracer MP581 specifications
Weight
Operating temperature
Storage temperature
Humidity
Altitude
Installation
Pollution
High-voltage power require-
ments
Weight
Analog to digital conversion
Digital to analog conversion
Microprocessor
Processor clock speed:
Memory
Clock
Battery
15 lb (7 kg)
From –40°F to 120°F (–40°C to 49°C)
From –58°F to 203°F (–50°C to 95°C)
10–90% non-condensing
6500 ft (2000 m)
Category 3
Degree 2
North America: 120 Vac, 1 A maximum, 1
phase
Mounting surface must be able to support
25 lb (12 kg)
12 bit
12 bit
Motorola MC68332
20 MHz
RAM: 256 kB (16-bit word)
EEPROM: 256 kB (8-bit word)
Flash: 1 MB (16-bit word)
Crystal controlled 32.768 kHz
None required
BAS-APG001-EN