Details Of Each Of The Parameters - Sharp JW-20FL5 User Manual

Fl-net module (board)
Table of Contents

Advertisement

Chapter 12: Parameters

12-2 Details of each of the parameters

(1) Enable/disable the use of the transmission buffer (Setting parameter address 37
Select whether to enable/disable the buffer for each message by entering the appropriate value at
parameter address 37
Message other than transmission
Transmission
message
* 80 to 83
Relationship between messages and transaction codes.
Message
Messages
other than
transmission
Transmission
messages
12
(2) Token monitor time (parameter address 04
Set the token monitor time as follows, based on the number of bytes being sent by this station.
- 0 to 5K bytes: 10 ms
- 5K to 10K bytes: 30 ms
- 10K bytes or more: 40 ms
.
(8)
Message
Messages other than SHARP's proprietary
message format
Computer link function
SHARP's
proprietary format
Remote function
are the valid values for parameter address 37
(H)
Transaction code (TCD)
60000 to 65202 (request)
65203 to 65215 (response)
0 to 999
1000 (request computer link function: SHARP's
proprietary function)
1001 (request remote function: SHARP's proprietary
function)
1002 to 1199
1200 (response of computer link function: SHARP's
proprietary function)
1201 (response of remote function: SHARP's
proprietary function)
1202 to 59999
transmission buffer
80
(H)
(Transmission buffer...
.
(8)
(Transmission buffer...
)
(8)
12-2
)
(8)
Selection of
*
81
82
83
(H)
(H)
(H)
: Used,
: Not used)
Use selection of
transmission type buffer
80
81
82
(H)
(H)
(H)
X
X
X
X
O
X
O
O
O
X
X
O
X
X
O
O
O
O
O
O
O
X
X
O
O
O
O
: Used,
: Not used)
83
*
(H)
X
O
O
O
O
O
O
O
O

Advertisement

Table of Contents
loading

This manual is also suitable for:

Jw-20fltJw-50flZ-336j

Table of Contents