Appendix B. Troubleshooting

Appendix B.1. ProducerID with FieldServer device as Producer

During testing it has been observed that a 90-30 PLC required that the ge_ProducerID parameter was set to the
same value as the IP Address of the FieldServer.

Appendix B.2. Produced Time Stamp

The GE-EGD (Ethernet Global Data) driver always sets the timestamp of produced data to the time of the Field
Server Device. The nanoseconds portion of the time stamp is always set to zero.

Appendix B.3. Status Values

The status of the EGD Exchange may be monitored in the GE PLC. The status value is well documented in GFK-
1541 Chapter 4.4. During testing, using the Field Server device as a producer and the GE Device as a consumer the
following status values were observed.
0 -> The exchange had never been consumed
1 -> Normal
4 -> Length of produced and consumed exchange not equal - Different messages with the same exchange ID.
6. -> Timeout.

Appendix B.4. Error Messages

Multiple protocol drivers may exist on a FieldServer. Each driver may produce its own error messages and the
FieldServer itself may produce error messages.
Message
EGD:#1 Error. Can't init UDP.
EGD:#2 Error. Can't get a socket.
EGD:#3 Error. Protocol does not
support active polling. Change
function for mapDesc=<%s>
EGD:#4
Error.
Producer
required for mapDesc=<%s>
EGD:#5
Error.
Exchange
required for mapDesc=<%s>
EGD:#6
FYI.
No
data
specified. Defaulted to <Byte>
EGD:#7 FYI. Data type not
recognized. Defaulted to <Byte>
for mapDesc=<%s>
4
Edit the CSV file, download to the FieldServer and restart the FieldServer for the changes to take effect.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com
Action
This is a fatal error. The FieldServer needs to be re-initialized or you need
technical support from FieldServer Technologies.
The rdbc/rdb/rdbx functions are not supported by this protocol. The device
you wish to poll must be configured to 'produce' its data and this driver will
'consume' the data using passive Map Descriptors.
ID
Each Map Descriptor requires a producerID.
ID
Each Map Descriptor requires an exchangeID.
type
This is a warning only. You can eliminate the warning by editing the CSV file.
Page 19 of 23
4
4
4
4

Advertisement

Table of Contents
loading

Table of Contents