DocuPrint 96/DocuPrint 96MX LPS power receptacle requirements

Electrical environment
U.S. and Canada 60 Hz
International 50 Hz
3-18
All power outlets must be dedicated only to this equipment. Ensure
that each power cord has a separate circuit.
You must use a power cord assembly (ELCI, RCD Inline, 220 VAC)
when using a source other than the system controller to provide
power to your keyboard/display. Contact your sales and service
representative to ensure the proper assembly is ordered and
installed.
Ensure that the power cord configurations match your receptacle
requirements (tables 3-7 and 3-8).
50 Hz systems: Consult with your local service representative to
determine the type of plug and receptacle to use with your 50 Hz
printer and system controller.
Table 3-7.
Electrical environment
U.S. and Canada 60 Hz
International 50 Hz WYE
International 50 Hz DELTA
Table 3-8.
Voltage
208/240, 1 Phase or
220/230 (L1-L2)
220/230, 1 Phase
XEROX DOCUPRINT 96/DOCUPRINT 96MX LPS INSTALLATION PLANNING GUIDE
Printer power receptacle requirements
Voltage/current
120/240/50A or
120/208/50A
380, 400, 415/20A (WYE), 3
Phase, 5 wire
220, 230, 240/30A (DELTA),
3 Phase, 4 wire
System controller and peripheral cabinet power
receptacle requirements
Current
15A
15A
Receptacle
NEMA 14-50R
Per local code
Per local code
Receptacle
NEMA 6-15R or
ANSI C73,
20R
Per local code