Table 32
Liebert CRV electrical data - 60Hz (Amps)
Air-Cooled Units
CR035RA
Voltage
460/3/60
208/3/60
Cooling with Dehumidifying, Condensate Pump, Reheat; with or without Humidifier
FLA
31.7
62.0
WSA
38.6
75.4
OPD
50
100
Cooling with Dehumidifying, Condensate Pump and Humidifier; NO Reheat
FLA
27.9
53.8
WSA
32.9
63.1
OPD
50
Cooling with Dehumidifying and Condensate Pump, NO Reheat, NO Humidifier
FLA
24.2
45.4
WSA
29.2
54.7
OPD
45
Cooling with Dehumidifying and Reheat; NO Condensate Pump, NO Humidifier
FLA
30.5
59.7
WSA
37.4
73.1
OPD
50
100
Cooling with Dehumidifying, NO Condensate Pump, NO Reheat, NO Humidifier
FLA
23.0
43.1
WSA
28.0
52.4
OPD
45
NOTICE
Risk of exceeding line-to-ground limit. Can cause equipment damage.
The electrically commutated (EC) motors included in 480V CR035 and CR040 units are
suitable for connection to power supplies with 300V or less line to ground potential. Excess
line-to-ground voltage can cause capacitor failure internal to the motors.
• Power supplies such as 480V WYE with solidly grounded neutral have 277V line to ground
and are acceptable.
• Power supplies such as 480V WYE with high resistance (or impedance) ground, 480V delta
without ground or with floating ground, 480V delta with corner ground or 480V delta with
grounded center tap will exceed the 300V line-to-ground limit.
Table 33
Calibration of electrical components
Refrigeration Circuit
Item No.
18-19
14
3
D
ATA
CR020RA
460/3/60
208/3/60
24.3
51.0
29.3
61.6
35
80
20.5
42.8
23.6
49.3
90
35
70
16.8
34.4
19.9
40.9
90
30
60
23.1
48.7
28.1
59.3
35
80
15.6
32.1
18.7
38.6
80
30
60
Component
High Pressure
Range 045 barg
Transducer
Output 05V
Low Pressure
Range 017.3 barg
Transducer
Output 05V
STOP 38.7±1 barg
High Pressure
START 30.0±1.5 barg
Switch (HP)
(fixed setting manual reset)
Clogged Filter
Setpoint range 0.54 mbar
Differential Pressure
Filter G4 = 2 mbar
Switch (CF)
Water/Gylcol-Cooled Units
CR035RW
460/3/60
208/3/60
460/3/60
31.7
62.0
24.3
38.6
75.4
29.3
50
100
35
27.9
53.8
20.5
32.9
63.1
23.6
50
90
35
24.2
45.4
16.8
29.2
54.7
19.9
45
90
30
30.5
59.7
23.1
37.4
73.1
28.1
50
100
35
23.0
43.1
15.6
28.0
52.4
18.7
45
80
30
Setting
See Liebert iCOM
User Manual, SL-18835
123
Electrical Data
Chilled Water Units
CR020RW
CR040RC
208/3/60
460/3/60
51.0
11.7
61.6
14.6
80
20
42.8
7.9
49.3
9.9
70
15
34.4
4.2
40.9
4.6
60
15
48.7
10.5
59.3
13.1
80
15
32.1
3.0
38.6
3.4
60
15
Notes
Contact
®
Normally
Reset
Closed
Normally
Setting Ring
Closed
Liebert
208/3/60
24.9
31.1
35
16.7
20.9
25
8.3
9.1
15
22.6
28.3
30
6.0
6.8
15
®
CRV