10.0 L
COM
IEBERT I
The Liebert CRV is equipped with the most advanced Liebert iCOM control system. The large Liebert
iCOM display is standard on the Liebert CRV.
Each Liebert CRV contains a return air temperature and humidity sensor, supply air temperature
sensor and three remote rack sensors. Up to an additional 7 remote rack sensors can be added to the
sensor network. Each rack sensor takes two temperature readings and reports either the average or
the maximum temperature of the two sensors.
The 2T rack temperature sensors provide feedback to the cooling unit about the condition of the air
entering the server racks. This information allows the Liebert CRV to ensure it is providing just
enough cold air to each rack, virtually eliminating hot spots. Overcooling and excessive airflow are
avoided, greatly reducing unnecessary energy consumption.
Each Liebert CRV includes three 2T rack temperature sensors to monitor three racks. A total of ten
2T temperature sensors can be connected to each cooling unit to monitor every rack a Liebert CRV is
protecting. When multiple cooling units are connected in a Unit-to-Unit iCOM control network, all
sensor data is shared to optimize their performance as a system.
2T rack sensors can also be initially installed on empty racks reserved for future growth with the
control set to ignore these sensor readings. The extra 2T temperature sensor readings can also be
displayed on the local display and reported remotely for monitoring purposes only; not impacting unit
operation. This function provides users with a built-in mini-monitoring system.
Table 22
Keyboard icons and functions
Icon
?
ESC
®
C
ONTROL
Key Name
Function
On/Off Key
Controls the operational state of the cooling unit.
Alarm Key
Silences an alarm.
Help Key
Accesses integrated Help menus.
ESCape Key
Returns to the previous display view.
Enter Key
Confirms all selections and selects icons or text.
Increase Key
Moves upward in a menu or increases the value of a selected parameter.
(Up Arrow)
Decrease Key
Moves downward in a menu or reduces the value of a selected parameter.
(Down Arrow)
Left and Right
Navigates through text and sections of the display.
Arrow Keys
Blinking Red—Active, unacknowledged alarm exists
Upper LED
Solid Red—Active, acknowledged alarm exists
Amber—Power is available to the unit; unit is NOT operating
Lower LED
Green—Unit is operating with no alarms
51
®