Figure 60 Setpoints Parameters Screen - Page 4; Table 26 Unit Diary Parameters - Emerson Liebert CRV User Manual

24-inch wide, air-cooled, water/glycol-cooled and chilled water
Hide thumbs Also See for Liebert CRV:
Table of Contents

Advertisement

Figure 60 Setpoints parameters screen - Page 4

SETPOINTS (page 4 of 4)
S134
S135
S136
S137
S138
S139
S140
S141
S142
S143
S144
MIN at CFC for EC Fan—This parameter can provide an offset to the minimum fan speed at the
minimum call for cooling. When set to 0 / 100 the MIN speed is reached when the call for fan is at 0%;
and the STD speed is reached when the call for fan reaches 100%.
For example, if the minimum is set to 20 and the standard is set to 90, the fan speed MIN is reached
earlier (the fan operates on lower speed compared to the calculated call for fan), and the STD speed is
reached faster when compared to the calculated call for fan.
STD at CFC for EC Fan—This parameter can provide an offset to the minimum fan speed at the
minimum call for cooling. When set to 0 / 100 the MIN speed is reached when the call for fan is at 0%;
and the STD speed is reached when the call for fan reaches 100%.
High Temp Limit Approach—This parameter sets the sensor that controls the fan speed maximum
override. This can be set to Disable, Supply or Return.
NOTE
The Liebert CRV fans are oversized and can be used to help protect equipment in emergency
situations, such as high temperature and a single fan failure.
High Temp Limit Approach at— This parameter sets the temperature when the units fan speed
can operate above the maximum speed. The maximum override speed during this mode is set in
parameter A157 (Advanced menus).
Ball Valve Setpoint Offset—This parameter adjusts the operating compressor discharge pressure
by changing the targeted range of control. Available only on water-cooled units.
Unit Diary—Large Display Only
Shows all entered program changes and maintenance performed on the unit.
Table 26
Unit diary parameters
Large Display
Page 1 of 1
Text entered with iST
®
(Liebert iCOM
Service Tool)
®
Liebert
CRV
PASSWORD
(Actual Level 0)
MIN at CFC for EC Fan
STD at CFC for EC Fan
High Temp Limit Approach
High Temp Limit Approach at
Ball Valve Setpoint Offset
for next/previous unit
then
to change parameter
Function
Small Display
N/A
Supply
to select parameter
Range
Imperial (metric)
-
72
Liebert iCOM
UNIT 01
????
0%
100 %
2°F
0psig
to confirm
®
Control