Figure 73 Set Alarms Parameters Screen - Page 1 - Emerson Liebert CRV User Manual

24-inch wide, air-cooled, water/glycol-cooled and chilled water
Hide thumbs Also See for Liebert CRV:
Table of Contents

Advertisement

Figure 73 Set alarms parameters screen - Page 1

SET ALARMS (page 1 of 4)
S201
S202
S203
S204
S205
S206
S207
S208
S209
S210
S211
Temp/Hum Events—This parameter enables or disables all of the temperature and humidity
events.
High Supply Temperature—This parameter sets the high temperature threshold that will trigger
an alarm on the Liebert iCOM
Low Supply Temperature—This parameter sets the low temperature threshold that will trigger an
alarm on the Liebert iCOM local display and any monitoring system that may be connected.
High Return Temperature—This parameter sets the threshold temperature when a return high
temperature alarm will occur.
High Return Humidity—This parameter sets the threshold humidity when a return high humidity
alarm will occur.
Low Return Humidity—This parameter sets the threshold humidity when a return low humidity
alarm will occur.
High CW Temperature—This parameter sets the threshold chilled water when a return high
chilled water temperature alarm will occur.
PASSWORD
(Actual Level 0)
Tem/Hum Events
High Supply Temperature
Low Supply Temperature
High Return Temperature
High Return Humidity
Low Return Humidity
High CW Temperature
for next/previous unit
then
to change parameter
local display and any monitoring system that may be connected.
®
Enabled
to select parameter
83
Liebert iCOM
UNIT 01
????
80 °F
46 °F
104 °F
60 %
15 %
°F
to confirm
Liebert
®
Control
®
CRV