Table 19 Unit Connections, Water/Glycol-Cooled Models - Emerson Liebert CRV User Manual

24-inch wide, air-cooled, water/glycol-cooled and chilled water
Hide thumbs Also See for Liebert CRV:
Table of Contents

Advertisement

Table 19
Unit connections, water/glycol-cooled models
Unit Connections
CS
Water/Glycol Coolant Supply
CR
Water/Glycol Coolant Return
GD
Gravity Coil Pan Drain
GDH Gravity Humidifier Drain
HS
Humidifier Supply
CP
Condensate Pump
HVT High Voltage Top Connection
High Voltage Bottom Entrance
HVB
(feed through the base of the unit)
LVT
Low Voltage Top Connection
Low Voltage Bottom Entrance
LVB
(feed through the base of the unit)
Low Voltage Bottom Entrance
LVB2
(feed through the base of the unit)
Source: DPN001793, Rev. 2
®
Liebert
CRV
CR20W (50Hz)
CR35W (50Hz)
32mm GAS F
32mm GAS F
20mm I.D.
22mm I.D.
1/2" GAS F (top connection)
3/4" GAS F (bottom connection)
1/2" GAS F
Combination Knockout Hole
Diameter 1-3/8" (35mm)
1-3/4" (44.5mm) and 2-1/2" (63.5mm)
Hole Diameter 2-1/2" (63.5mm)
Hole Diameter
7/8" (22mm) 2 places
Hole Diameter 1-7/64" (28mm)
2 places
34
Water Connections
CR20W (60Hz)
CR35W (60Hz)
1-1/4" FPT
1-1/4" FPT
1" MPT
N/A
1/2" FPT (top connection)
1/4" Compression Fitting
(bottom connection)
1/2" FPT
Combination Knockout Hole
Diameter 1-3/8" (35mm)
1-3/4" (44.5mm) and 2-1/2" (63.5mm)
Knockout Hole Diameter 2-1/2" (63.5mm)
Knockout Hole Diameter
7/8" (22mm) 2 places
Knockout Hole Diameter
1-3/32" (27.8mm) 2 places
Knockout Hole Diameter
1-3/4" (44.5mm) 1 place