Return T Sensor PTC or NTC—This parameter selects the type of sensor being used for the return
air sensor.
Return T Sensor—This parameter can provide an offset to the actual sensor reading to calibrate the
units sensor to other sensors.
Calibrated Return T Sensor—This parameter is the reading after the offset has been added to or
subtracted from the actual sensor reading.
Supply T Sensor PTC or NTC—This parameter sets the type of sensor that is connected to the
unit. It is set at the factory as NTC and should be changed only by a certified Emerson technician.
Supply T Sensor—This parameter can provide an offset to the actual sensor reading to calibrate the
unit's sensor to other sensors.
Calibrated Supply T Sensor—This parameter is the reading after the offset has been added to or
subtracted from the actual sensor reading.
CW T Sensor—This parameter can provide an offset to the actual sensor reading to calibrate the
unit's sensor to other sensors.
Calibrated CW T Sensor—This parameter is the reading after the offset has been added to or
subtracted from the actual sensor reading.

Figure 79 Sensor calibration / setup parameters - Page 3

SENSOR CALIBRATION/SETUP (page 3 of 4)
S623
S624
S625
S626
S627
S628
S629
S630
S631
S632
S633
This unit can be equipped with a total of 20 rack sensor readings or 10 2T temperature sensor
modules. This menu provides the ability to calibrated by entering a negative or positive offset. The
calibrated reading is displayed in the far right column. If a value is not shown in the far right column,
then the sensor is either not setup correctly or is not connected.
PASSWORD
Actual Level 0)
Rack Temperature Sensor 1
Rack Temperature Sensor 2
Rack Temperature Sensor 3
Rack Temperature Sensor 4
Rack Temperature Sensor 5
Rack Temperature Sensor 6
Rack Temperature Sensor 7
Rack Temperature Sensor 8
Rack Temperature Sensor 9
Rack Temperature Sensor 10
for next/previous unit
then
to change parameter
+0°F
+0°F
+0°F
+0°F
+0°F
+0°F
+0°F
+0°F
+0°F
+0°F
to select parameter
87
Liebert iCOM
UNIT 01
????
77°F
78°F
77°F
77°F
78°F
°F
°F
°F
°F
°F
to confirm
Liebert
®
Control
®
CRV

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents