2.0
I
NSTALLATION
2.1
Mechanical Considerations
2.1.1
Positioning the Liebert XDP
Install the Liebert XDP according to the site specific documentation and secure the unit to the floor.
The Liebert XDP can be installed near a wall or another Liebert XDP. However, there must be at
least 3 feet (92cm) clearance in front of the Liebert XDP as service access for components in the unit.
For additional technical information, refer to the System Design and Configuration Document for the
™
Liebert XD
System, SL-16655. The document is available in electronic format at Liebert's Web site,
www.liebert.com
Figure 7
Dimensions
A
Overall
C
Side Panel
D
Unit Base
Unit Dimensional Data
Table 2
Liebert XDP dimensions
Model
50/60Hz
A
XDP160
38 (965)
* The dimension does not include the bezel of the disconnect switch.
, as well as from your local Emerson representative.
B
Overall
Height
of Unit
E
Unit Base
Dimensional Data, inches (mm)
B*
C
34 (864)
33-1/8 (841)
F
(127mm)
1" (25mm)
2-3/8"
(60mm)
Floor Cutout Dimensions
The shaded area indicates
a recommended clearance
of 36" (914mm) for component
access.
D
E
33 (838)
36 (914)
9
E
5"
11"
(279mm)
DPN001598
Pg. 2, Rev. 7
Shipping Weight, lb. (kg)
H
Domestic
78 (1981)
1020(462)
Installation
D
Export
1083 (491)