Module Led Indication; Table 2 Guide To Leds - Emerson Nfinity 208 User Manual

208/240v 60hz 12 to 20 kva ups systems
Table of Contents

Advertisement

4.2

Module LED Indication

Every Battery, Power and Control Module features two LEDs to help inform the user of the module
status, as shown below left. Refer to Table 2 for details.
Control Module
Power Module
Battery Module
Green Status LED
Yellow Fault LED
Green Status LED
Yellow Fault LED
Green Status LED
Yellow Fault LED
33
Table 2
Guide to LEDs
Status
Fault
LED
LED
(Green)
(Yellow)
OFF
OFF
OFF
ON
FLASHING
OFF
FLASHING
FLASHING
FLASHING
ON
OFF
FLASHING
ON
OFF
ON
ON
ON
FLASHING
*
If this persists for more than 30 seconds, check to verify the
lever is in the down position, otherwise the module is faulty.
** If both green and yellow LEDs are flashing for more than 30
seconds, then reinsert module.
Troubleshooting
Module Status
Module not inserted into
frame. System is OFF.
Module is initializing
(max 30 seconds*).
Normal Operation
Module is in start-up
qualification mode or module
warning. **
Module failed and is off-line.
Abnormal operation,
re-insert module.
If this persists, contact
Liebert Global Services at
1-800-543-2378.

Hide quick links: