Operating; Instructions; Controls And Indicators; Display Controls - Emerson Nfinity 208 User Manual

208/240v 60hz 12 to 20 kva ups systems
Table of Contents

Advertisement

3.0
O
PERATING
3.1

Controls and Indicators

3.1.1

Display Controls

The User Interface Module informs you of the status of the UPS and lets you configure the UPS to
your own needs or preferences.
The module consists of a series of Status LEDs, an LCD display window (four lines of 20 characters
each), and buttons for navigation, as displayed below.
Fault/Warning LED
Alarm
Silence
Button
Buttons
Refer to the legend below to properly navigate the
Nfinity User Interface.
Up
- Navigates cursor on display menus
Down
Escape
- Returns to previous display screen
ESC
Enter
- Selects displayed information
Standby
- Enables / disables output power
Alarm
- Mutes the audible alarm
Silence
I
NSTRUCTIONS
Navigation Buttons
Status LEDs
LCD Display
Window
Fault/Warning and Status LEDs
Refer to the legend below to indicate occurrence
when an LED is lit.
Fault/Warning
Solid - A UPS fault condition has occurred.
Flashing - A Warning has occurred. Consult event log.
AC Input - AC utility is available.
On Bypass - The Bypass is supplying the power.
Inverter On - The inverter is supplying the power.
On Battery - Battery is supplying power to the inverter.
AC Output - Power is available to supply the load.