Specifications; Product Warranty Registration - Emerson Nfinity 208 User Manual

208/240v 60hz 12 to 20 kva ups systems
Table of Contents

Advertisement

6.0
S
PECIFICATIONS
General & Environmental
Unit Rating
Conducted and Radiated EMC Levels
Compliant Safety Standards
Compliant Immunity Standards
Mechanical
Width
Dimensions
Depth
Height
Environmental
Operating Temperature (max)
Relative Humidity
Maximum operating altitude
Nominal heat dissipation
Acoustic noise level
Input Data
Nominal input voltage
Voltage Range (Typical)
Power factor
Input frequency (nominal)
Input frequency range
Battery Module
Number of lead acid batteries
Number of battery cells
Battery capacity
Autonomy time (full load)
Maximum charge current (full load)
Nominal Voltage
Recharge Time
Output Data
Output voltage
Voltage regulation
Voltage stability (100% step load)
Recovery time
Voltage distortion
Output frequency
Efficiency at 100% load
Output overload capability
6.1

Product Warranty Registration

To register for warranty protection:
• Visit the Quick Links section of our Web site at:
http://www.liebert.com
• Click on Product Warranty Registration and fill in the form.
If you have any questions, please contact us at:
US: 800-222-5877
Outside the US: 614-841-6755
upstech@liebert.com
Units
kVA
12
kW
8.4
Units
in (mm)
Units
C (F)
%
M (ft.)
BTU/Hr
3,186
dBA
Units
VAC
208VAC nominal: operating voltage range variable based on output loading percentages
% UPS Load
80 – 100%
60 – 80%
30 – 60%
0 – 30%
Cos
Hz
Hz
Units
A/hr
minutes
6 (With an equal number of Battery & Power Modules, in a non-redundant configuration)
A
VDC
Hrs
Units
VAC
%
%
msec
%
Hz
%
%
37
Configuration
16
11.2
FCC Part 15, Class A
UL 1778; c-UL
IEEE C62.41, Category B
20 (508)
28 (711)
54 (1372)
0° - 40° (32° - 104°)
0-95% non-condensing
3,000 (10,000)
4,248
5,903
<62 @ 1 meter
208 or 240
>.98
60
40-70
10
60
9
3
120
Typically 6 (to 90% capacity)
208/120 or 240/120
±3
±7
96
<3 THD, linear load
<7 THD, non-linear load
60
89
110 - 125% for 10 min
126-150% for 10 sec
151 - 200% for 2 cycles

Specifications

20
20
14
16
6,748
Input Voltage
170 VAC
144 VAC
127 VAC
110 VAC

Hide quick links: